72
The chlorine value not increase at least with 0.05 ppm
even if the chlorine dosing pump is running full time for
“Max On time”. In this particular case, the error is cleared
only when the controller is restarted. This could be caused
by absence of the chlorination agent, the malfunction of
the dosing pump or malfunction of the detector.
Check the presence of the magnet barr, check the reagent
level, check the reagent pump tubes, clean cell, observe
if the sample flow in the cell, edit the “Low Point”. Value,
check the chlorine dosing pump, replace the cell.
“
pH Out of RpH Out of R
pH Out of RpH Out of R
pH Out of R
angeange
angeange
ange” on LCD and “
pH ErrpH Err
pH ErrpH Err
pH Err” on SMS
pH value is outside range (0.00 to 14.00 pH).
Verify the connections; Change the pH probe.
“
ORP Out of RORP Out of R
ORP Out of RORP Out of R
ORP Out of R
angeange
angeange
ange” on LCD and “
ORP ErrORP Err
ORP ErrORP Err
ORP Err” on SMS
ORP value is outside range (0 to 2000 mV).
Verify the sample ORP; verify ORP probe connections,
Change the ORP probe.
“
TT
TT
T
emp. Out of Remp. Out of R
emp. Out of Remp. Out of R
emp. Out of R
angeange
angeange
ange” on LCD and “T
emp Erremp Err
emp Erremp Err
emp Err” on SMS
Temperature value is outside range (0.0 °C to 75.0 °C).
Verify the sample temperature, verify the pH probe con-
nector; change the pH probe.
“
Conc. Out of RConc. Out of R
Conc. Out of RConc. Out of R
Conc. Out of R
angeange
angeange
ange” on LCD and “
Cl ErrCl Err
Cl ErrCl Err
Cl Err” on SMS
Chlorine value is outside range (0.00 to 5.00 mg/L).
The chlorine concentration is too high.
ALARM MESSAGES
“
High ChlorineHigh Chlorine
High ChlorineHigh Chlorine
High Chlorine” on LCD and “
H ClH Cl
H ClH Cl
H Cl” on SMS
The concentration is over the Alarm High setpoint.
Change the setpoint; verify the chlorine dosing.
“
Low ChlorineLow Chlorine
Low ChlorineLow Chlorine
Low Chlorine” on LCD and “
L ClL Cl
L ClL Cl
L Cl” on SMS
The concentration is under the Alarm Low setpoint.
Change the setpoint, verify the chlorine dosing, wait for
PCA to adjust the value.
“
High pHHigh pH
High pHHigh pH
High pH” on LCD and “
H pHH pH
H pHH pH
H pH” on SMS
The pH is over the Alarm High setpoint.
Change the setpoint; verify the pH dosing; verify if acid/base
dosing is correctly set; wait for PCA to stabilize the value.
“
Low pHLow pH
Low pHLow pH
Low pH” on LCD and “
L pHL pH
L pHL pH
L pH” on SMS
The pH is under the Alarm Low setpoint.
Change the setpoint; verify the pH dosing; verify if acid/
base dosing is correctly set; wait for PCA to adjust the value.